XLPE Insulated, LSZH Sheathed, Overall Screened & Armoured Instrumentation Cables (Single triple)

RE-2X(St)HSWAH 70°C / 300 V

Application

These cables are used for transmission of analoge and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroluem plants, etc.

These cables are used in the environments which have no corrosive gases are emitted in the event of fire. In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low. Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g. public mains electricity supply. With blue sheath it is suitable for intrinsically safe systems. These cables are not recommended for direct burial. They are for indoor and outdoor installation, in dry and wet l°Cations; on racks, trays, in conduits.

Standards

Basic design to EN 50288-7

Fire Performance

Flame Retardance (Single Vertical Wire Test) EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation(Vertically-mounted bundled wires & cable test) EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454
Sunlight Resistance UL 1581 section 1200
Oil Resistance ICEA S-73-532**

Note: Asterisk * denotes superseded standard, ** denotes Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation, *** denotes optional.

Voltage Rating

300V

Cable Construction

Conductor : Annealed copper solid or plain copper stranded to IEC 60228 Class 2.

Insulation : Extruded cross-linked XLPE compound, EN 50290. 2-29.

Pair : Two conductors twisted to form a pair Lay-up: Pairs laid up in layers of optimum pitch

Separator : Polyester tape

Overall Screen : Aluminium/polyester tape with tinned copper drain wire, 0.5mm²

Inner sheath : HFFR compound, EN 50290-2-27

Armour : Galvenized round steel wire, EN 10257-1

Outer Sheath : Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound typeSW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.

Colour Code

Insulation : Black / White / Red, continuously numbered on white core(1, 2..)for multitriples.

Outer Sheath : Black or blue for intrinsically safe systems

Physical and Thermal Properties

Temperature Range During Operation (Fixed State) : -30°C – +70°C

Temperature Range During Installation (Mobile State) : -5°C – +50°C

Minimum Bending Radius : 7.5 × Overall Diameter

Electrical Roperties

Conductor Area Size mm² 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.35 0.38 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) pF/m(Max.) 250
Capacitance unbalance(1 kHz) pF/500 m (Max.) 500
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Inductance mH/km(Max.) 1
Operating voltage Urms V 300
Test Voltage Core to Core V 1500
Core to Screen V 1500

Construction Parameterst

Caledonian Cable Code RE-2X(St)HSWAH
No. of Triples × 3 × Cross Section Nominal Insulation Thickness Nominal Inner Sheath Thickness Nominal Overall Diameter Over Inner Sheath Nominal Armour Wire Diameter Nominal Outer Sheath Thickness Nominal Overall Diameter Approx. Weight
  No. × 3 × mm² mm mm mm mm mm mm kg/km
RE-2X(St)HSWAH 1T0.5 1x3x0.50 0.35 0.8 5.4 0.9 1.3 9.8 200
RE-2X(St)HSWAH 1T0.75 1x3x0.75 0.38 0.9 6.1 0.9 1.3 10.5 220
RE-2X(St)HSWAH 1T1.0 1x3x1.0 0.4 0.9 6.6 0.9 1.3 11.0 244
RE-2X(St)HSWAH 1T1.3 1x3x1.3 0.45 0.9 7.2 0.9 1.3 11.6 268
RE-2X(St)HSWAH 1T1.5 1x3x1.5 0.45 0.9 7.5 0.9 1.3 11.9 293