H05BQ-F/H07BQ-F(NGMH11YÖ)

Application and Description

These cables are used for medium mechanical stress in dry, damp or wet areas, e.g. for connecting agricultural and commercial equipment, for connecting heaters where there is a danger of cable damage due to its contact with hot surfaces. The cable can also be used in electrical appliances such as drills, hand-held circular saws as well as in building sites and refrigeration plants.

H07BQ-F can commonly be found in other machinery in agriculture, building sites, docks and refrigeration plants. The robust PUR jacket adds abrasion, notch and tear resistance as well as chemical resistance to oils, fats, petrol, water, ozone, UV radiation, hydrolysis and microbes. Common European designation is NGMH11YÖ.

Standard and Approval

<HAR> HD22.10 S1, VDE-0282 Part-10, CEI 20-19 p.10, CE low voltage directive 73/23/EEC & 93/68/EEC., IEC 60245-4, ROHS compliant

Cable Construction

Fine bare or tinned copper strands

Strands to VDE-0295 Class-5, IEC 60228 and HD383 Class-5

Rubber compound insulation E16 to VDE-0282 Part-1

Color coded to VDE-0293-308

Conductors stranded in layers with optimal lay-length

Green-yellow earth core in the outer layer

Polyurethane/PUR outer jacket TMPU- orange (RAL 2003)

Technical Characteristics

Working voltage : 300/500 volts(H05BQ-F), 450/750 volts(H07BQ-F)

Test voltage : 2000 volts(H05BQ-F), 2500 volts(H07BQ-F}

Flexing bending radius : 5 x Ø

Fixed bending radius : 3 x Ø

Flexing Temperature : -40º C to +80º C

Fixed Temperature : -50º C to +90º C

Short circuit Temperature : +250º C

Flame retardant : IEC 60332.1

Insulation resistance : 20 MΩ x km

Cable Parameter

AWG No. of Cores x Nominal Cross Sectional Area Nominal Thickness of Insulation Nominal Thickness of Sheath Nominal Overall Diameter Nominal Copper Weight Nominal Weight
  # x mm² mm mm mm kg/km kg/km
H05BQ-F
18(24/32) 2 x 0.75 0.6 0.8 5.7 - 7.4 14.4 52
18(24/32) 3 x 0.75 0.6 0.9 6.2 - 8.1 21.6 63
18(24/32) 4 x 0.75 0.6 0.9 6.8 - 8.8 29 80
18(24/32) 5 x 0.75 0.6 1.0 7.6 - 9.9 36 96
17(32/32) 2 x 1 0.6 0.9 6.1 - 8.0 19.2 59
17(32/32) 3 x 1 0.6 0.9 6.5 - 8.5 29 71
17(32/32) 4 x 1 0.6 0.9 7.1 - 9.3 38.4 89
17(32/32) 5 x 1 0.6 1.0 8.0 - 10.3 48 112
H07BQ-F
16(30/30) 2 x 1.5 0.8 1.0 7.6 - 9.8 29 92
16(30/30) 3 x 1.5 0.8 1.0 8.0 - 10.4 43 109
16(30/30) 4 x 1.5 0.8 1.1 9.0 - 11.6 58 145
16(30/30) 5 x 1.5 0.8 1.1 9.8 - 12.7 72 169
14(50/30) 2 x 2.5 0.9 1.1 9.0 - 11.6 101 121
14(50/30) 3 x 2.5 0.9 1.1 9.6 - 12.4 173 164
14(50/30) 4 x 2.5 0.9 1.2 10.7 - 13.8 48 207
14(50/30) 5 x 2.5 0.9 1.3 11.9 - 15.3 72 262
12(56/28) 2 x 4 1.0 1.2 10.6 - 13.7 96 194
12(56/28) 3 x 4 1.0 1.2 11.3 - 14.5 120 224
12(56/28) 4 x 4 1.0 1.3 12.7 - 16.2 77 327
12(56/28) 5 x 4 1.0 1.4 14.1 - 17.9 115 415
10(84/28 2 x 6 1.0 1.3 11.8 - 15.1 154 311
10(84/28 3 x 6 1.0 1.4 12.8 - 16.3 192 310
10(84/28 4 x 6 1.0 1.5 14.2 - 18.1 115 310
10(84/28 5 x 6 1.0 1.6 15.7 - 20.0 173 496