CC-Link 1.10 Cable
 Applications
 CC-Link(R) (Control & Communication Link) is a field network system that processes both control and information data at high speed, to provide efficient, integrated factory and process automation. CC-Link is particularly popular in Asia and is used worldwide for time critical applications . CC-Link is certified by CLPA and ensures product compatibility.
 Construction
 
 
   
   
     | Type | 
     3 x 20AWG Cable | 
   
   
     | Inner Conductor | 
     Plain copper conductors 20(7)AWG | 
   
   
     | Conductor Insulation | 
     Foamed PE with a hard skin | 
   
   
     | Stranding Element | 
     - | 
   
   
     | Core Wrapping | 
     Polyester taped | 
   
   
     | Shielding | 
     Aluminium foil | 
   
   
     | Total Shielding | 
     Tinned copper wire braid – 78% optical coverage | 
   
   
     | Drain Wire | 
     22(19)AWG tinned copper | 
   
   
     | Outer Jacket Material | 
     PVC / PE | 
   
   
     | Core Identification | 
     Yellow, White, Blue | 
   
   
     | Sheath colour | 
     Red | 
   
   
 
 Electrical Data
 
 
   
     | CharacteristicImpedance@1MHz | 
     110 Ω ± 10Ω | 
   
   
     | Conductor Resistance | 
     36.0 Ohm/km max. | 
   
   
     | Insulation Resistance | 
     10.0GOhm x km min. | 
   
   
     | Mutual Capacitance@1 KHz | 
     60.0 nF/km nom. | 
   
   
     | Working Voltage | 
     Max:300v | 
   
   
     | Test Voltage | 
     2 KV | 
   
   
     |   | 
     156 Kbit/s | 
     1200m | 
   
   
     |   | 
     625 Kbit/s | 
     600m | 
   
   
     | Data Rate | 
     2.5 Mbit/s | 
     200m | 
   
   
     |   | 
     5.0 Mbit/s | 
     110-150m | 
   
   
     |   | 
     10.0 Mbit/s | 
     50-100m | 
   
   
     | Attenuation | 
     1MHz | 
     1.6dB/100m | 
   
   
     |   | 
     5MHz | 
     3.5dB/100m | 
   
   
 
 Technical Data
 
 
   
     | Weight | 
     approximately 76.0 kg/km | 
   
   
     | Min. Bending Radius (Laying) | 
     15 x OD mm | 
   
   
     | Operating Temp.Range, min. | 
     - 40 °C | 
   
   
     | Operating Temp.Range, max. | 
     +70 °C |