| Test |
Unit |
H07Z-K H07Z-R H07Z-U |
H05Z-K H05Z-U |
Thermosetting insulated, single-core cables |
Thermosetting insulated, twin, 3-core, 4-core and 5-core circular sheathed cables |
6241B 6242B 6243B |
| Voltage test on complete cable |
| Length of sample (min.) |
m |
20 |
20 |
20 |
20 |
20 |
| Period of immersion (min.) |
h |
1 |
1 |
1 |
1 |
1 |
| Temperature of water |
°C |
20 ± 5 |
20 ± 5 |
20 ± 5 |
20 ± 5 |
20 ± 5 |
| Applied voltage (a.c.) |
V |
2 500 |
2 000 |
2 500 |
2 500 |
2 000 |
| Time of application |
min |
15 |
15 |
15 |
15 |
15 |
| Voltage test on cores |
| Length of sample |
m |
— |
— |
20 |
20 |
20 |
| Period of immersion (min.) |
h |
— |
— |
1 |
1 |
1 |
| Temperature of water |
°C |
— |
— |
20 ± 5 |
20 ± 5 |
20 ± 5 |
| Applied voltage (a.c.) |
V |
— |
— |
2 500 |
2 500 |
2 000 |
| Time of application |
min |
— |
— |
5 |
5 |
5 |
| Insulation resistance |
| Length of sample |
m |
5 |
5 |
5 |
5 |
5 |
| Period of immersion (min.) |
h |
2 |
2 |
2 |
2 |
2 |
| Temperature of water |
°C |
90 ± 2 |
90 ± 2 |
90 ± 2 |
90 ± 2 |
90 ± 2 |
| Spark test |
| Result to be obtained |
|
No failure |
No failure |
No failure |
— |
— |
| Voltage test |
|
|
|
|
|
|
| Applied voltage a.c. |
V |
— |
— |
— |
2500 |
2000 |
| Applied voltage d.c. (min) |
V |
— |
— |
— |
5000 |
5000 |
| Duration of test |
min |
— |
— |
— |
5 |
5 |
| Result to be obtained |
|
— |
— |
— |
No breakdown |
No breakdown |