Technical Reference
Maximum resistance of conductor and armour for single-core cable having aluminum wire armour
| Nominal cross sectional area of conductor | Maximum resistance per km of cable at 20 °C | |||||
|---|---|---|---|---|---|---|
| Copper conductor | Aluminum conductor | Aluminum wire armour | ||||
| Cables with stranded copper conductor | Cables with solid aluminum conductor | |||||
| 600/1000 V | 1900/3300 V | 600/1000 V | 1900/3300 V | |||
| mm2 | Ω | Ω | Ω | Ω | Ω | Ω |
| 50 | 0.387 | 0.641 | 1.3 | 0.75 | 1.4 | 0.79 |
| 70 | 0.268 | 0.443 | 0.75 | 0.67 | 0.84 | 0.73 |
| 95 | 0.193 | 0.32 | 0.67 | 0.61 | 0.75 | 0.67 |
| 120 | 0.153 | 0.253 | 0.61 | 0.42 | 0.69 | 0.47 |
| 150 | 0.124 | 0.206 | 0.42 | 0.39 | 0.47 | 0.43 |
| 185 | 0.0991 | 0.164 | 0.38 | 0.37 | 0.42 | 0.4 |
| 240 | 0.0754 | 0.125 | 0.34 | 0.34 | 0.38 | 0.37 |
| 300 | 0.0601 | 0.1 | 0.31 | 0.31 | 0.35 | 0.34 |
| 400 | 0.047 | — | 0.22 | 0.22 | — | — |
| 500 | 0.0366 | — | 0.2 | 0.2 | — | — |
| 630 | 0.0283 | — | 0.18 | 0.18 | — | — |
| 800 | 0.0221 | — | 0.13 | 0.13 | — | — |
| 1 000 | 0.0176 | — | 0.12 | 0.12 | — | — |
Maximum resistance of conductor and armour for two-, three-, four- and five-core cables having wire armour
1) With stranded copper conductor
| Nominal cross sectional area of conductor | Maximum resistance per km of cable at 20 °C | ||||||
|---|---|---|---|---|---|---|---|
| Copper conductor | Aluminum conductor | Steel wire armour | |||||
| Cables with stranded copper conductors | |||||||
| Two-core | Three-core | Four-core | Five-core | ||||
| 600/1000 V | 600/1000 V | 1900/3300 V | 600/1000 V | 600/1000 V | |||
| mm2 | Ω | Ω | Ω | Ω | Ω | Ω | Ω |
| 1.5 | 12.1 | — | 10.2 | 9.5 | — | 8.8 | 8.2 |
| 2.5 | 7.41 | — | 8.8 | 8.2 | — | 7.7 | 6.8 |
| 4 | 4.61 | — | 7.9 | 7.5 | — | 6.8 | 6.2 |
| 6 | 3.08 | — | 7 | 6.7 | — | 4.3 | 3.9 |
| 10 | 1.83 | — | 6 | 4 | — | 3.7 | 3.4 |
| 16 | 1.15 | 1.91 | 3.7 | 3.5 | 1.9 | 3.1 | 2.2 |
| 25 | 0.727 | 1.2 | 3.7 | 2.5 | 1.7 | 2.0 2.3 | 1.8 |
| 35 | 0.524 | 0.868 | 2.6 | 2.3 | 1.8 | — | 1.6 |
| 50 | 0.387 | 0.641 | 2.3 | 2 | 1.3 | 1.8 | 1.1 |
| 70 | 0.268 | 0.443 | 2 | 1.8 | 1.2 | 1.2 | 0.94 |
| 95 | 0.193 | 0.32 | 1.4 | 1.3 | 1.1 | 1.1 | — |
| 120 | 0.153 | 0.253 | 1.3 | 1.2 | 0.76 | 0.76 | — |
| 150 | 0.124 | 0.206 | 1.2 | 0.78 | 0.71 | 0.68 | — |
| 185 | 0.099 1 | 0.164 | 0.82 | 0.71 | 0.65 | 0.61 | — |
| 240 | 0.075 4 | 0.125 | 0.73 | 0.63 | 0.59 | 0.54 | — |
| 300 | 0.060 1 | 0.1 | 0.67 | 0.58 | 0.55 | 0.49 | — |
| 400 | 0.047 0 | — | 0.59 | 0.52 | 0.5 | 0.35 | — |
2) With solid aluminum conductor
| Nominal cross-sectional area of conductor | Maximum resistance per km of cable at 20 °C | |||||
|---|---|---|---|---|---|---|
| Copper conductor | Aluminum conductor | Steel wire armour | ||||
| Cables with solid aluminum conductors | ||||||
| Two-core | Three-core | Four-core | ||||
| 600/1000 V | 600/1000 V | 1900/3300 V | 600/ 1000 V | |||
| mm2 | Ω | Ω | Ω | Ω | Ω | Ω |
| 1.5 | 12.1 | — | — | — | — | — |
| 2.5 | 7.41 | — | — | — | — | — |
| 4 | 4.61 | — | — | — | — | — |
| 6 | 3.08 | — | — | — | — | — |
| 10 | 1.83 | — | — | — | — | — |
| 16 | 1.15 | 1.91 | 4 | 3.8 | 2 | 3.4 |
| 25 | 0.727 | 1.2 | 4.1 | 2.7 | 1.9 | 2.4 |
| 35 | 0.524 | 0.868 | 2.9 | 2.5 | 1.9 | 2.2 |
| 50 | 0.387 | 0.641 | 2.6 | 2.2 | 1.4 | 1.9 |
| 70 | 0.268 | 0.443 | 2.3 | 1.9 | 1.3 | 1.3 |
| 95 | 0.193 | 0.32 | 1.6 | 1.4 | 1.2 | 1.2 |
| 120 | 0.153 | 0.253 | — | 1.2 | 0.82 | 0.82 |
| 150 | 0.124 | 0.206 | — | 0.86 | 0.76 | 0.74 |
| 185 | 0.099 1 | 0.164 | — | 0.76 | 0.71 | 0.67 |
| 240 | 0.075 4 | 0.125 | — | 0.68 | 0.64 | 0.59 |
| 300 | 0.060 1 | 0.1 | — | 0.63 | 0.59 | 0.54 |
| 400 | 0.047 0 | — | — | — | — | — |
Electrical Properties(600/1000 V)
1) Single core with copper conductor
| Nominal area of conductor | Single Core Stranded Copper Conductors | |||||
|---|---|---|---|---|---|---|
| Current Ratings | Approximate voltage drop per ampereper metre | |||||
| Direct in ground | In singleway ducts | Installed in air | Ground | Duct | Air | |
| mm² | amps | amps | amps | mV | mV | mV |
| 50 | 235 | 235 | 222 | 0.87 | 0.93 | 0.87 |
| 70 | 290 | 280 | 285 | 0.62 | 0.70 | 0.62 |
| 95 | 345 | 330 | 346 | 0.47 | 0.56 | 0.47 |
| 120 | 390 | 370 | 402 | 0.39 | 0.48 | 0.39 |
| 150 | 435 | 405 | 463 | 0.33 | 0.43 | 0.33 |
| 185 | 490 | 440 | 529 | 0.28 | 0.39 | 0.28 |
| 240 | 560 | 500 | 625 | 0.24 | 0.35 | 0.24 |
| 300 | 630 | 550 | 720 | 0.21 | 0.32 | 0.21 |
| 400 | 700 | 580 | 815 | 0.20 | 0.30 | 0.20 |
| 500 | 770 | 620 | 918 | 0.18 | 0.28 | 0.18 |
| 630 | 840 | 670 | 1027 | 0.17 | 0.26 | 0.17 |
| 800 | 888 | 692 | 1119 | 0.17 | 0.25 | 0.17 |
| 1000 | 942 | 735 | 1214 | 0.16 | 0.24 | 0.16 |
1) Single core with aluminum conductor
| Nominal area of conductor | Single Core Aluminum Conductors | |||||
|---|---|---|---|---|---|---|
| Current Ratings | Approximate voltage drop per ampereper metre | |||||
| Direct in ground | In singleway ducts | Installed in air | Ground | Duct | Air | |
| mm² | amps | amps | amps | mV | mV | mV |
| 50 | 175 | 180 | 162 | 1.40 | 1.60 | 1.40 |
| 70 | 220 | 220 | 207 | 0.98 | 1.00 | 0.98 |
| 95 | 260 | 260 | 252 | 0.72 | 0.79 | 0.74 |
| 120 | 295 | 295 | 292 | 0.58 | 0.66 | 0.60 |
| 150 | 330 | 330 | 337 | 0.48 | 0.57 | 0.49 |
| 185 | 375 | 365 | 391 | 0.39 | 0.49 | 0.41 |
| 240 | 435 | 410 | 465 | 0.31 | 0.42 | 0.34 |
| 300 | 490 | 455 | 540 | 0.27 | 0.38 | 0.29 |
| 400 | 540 | 480 | 625 | 0.35 | 0.38 | 0.25 |
| 500 | 580 | 510 | 714 | 0.31 | 0.35 | 0.22 |
| 630 | 630 | 540 | 801 | 0.28 | 0.32 | 0.20 |
2) Two cores with copper conductor
| Nominal area of conductor | Two Cores Stranded Copper Conductors | |||||
|---|---|---|---|---|---|---|
| Current Ratings | Approximate voltage drop per ampere per metre | |||||
| Direct in ground | In single way ducts | Installed in air | Ground | Duct | Air | |
| mm² | amps | amps | amps | mV | mV | mV |
| 16* | 140 | 115 | 115 | 2.9 | 2.9 | 2.9 |
| 25* | 180 | 145 | 152 | 1.9 | 1.9 | 1.9 |
| 35* | 215 | 175 | 188 | 1.3 | 1.3 | 1.3 |
| 50 | 255 | 210 | 228 | 1.0 | 1.0 | 1.0 |
| 70 | 315 | 260 | 291 | 0.7 | 0.7 | 0.7 |
2) Two cores with aluminum conductor
| Nominal area of conductor | Two Cores Aluminum Conductors | |||||
|---|---|---|---|---|---|---|
| Current Ratings | Approximate voltage drop per ampere per metre | |||||
| Direct in ground | In single way ducts | Installed in air | Ground | Duct | Air | |
| mm² | amps | amps | amps | mV | mV | mV |
| 25* | 135 | 110 | 112 | 3.1 | 3.1 | 3.1 |
| 35* | 165 | 130 | 138 | 2.2 | 2.2 | 2.2 |
| 50 | 195 | 155 | 166 | 1.7 | 1.7 | 1.7 |
| 70 | 240 | 195 | 211 | 1.1 | 1.1 | 1.1 |
| 95 | 288 | 237 | 254 | 0.8 | 0.8 | 0.8 |
3) Three cores with copper conductor
| Nominal area of conductor | Three Cores Stranded Copper Conductors | |||||
|---|---|---|---|---|---|---|
| Current Ratings | Approximate voltage drop per ampereper metre | |||||
| Direct in ground | In singleway ducts | Installed in air | Ground | Duct | Air | |
| mm² | amps | amps | amps | mV | mV | mV |
| 16 | 115 | 94 | 99 | 2.5 | 2.5 | 2.5 |
| 25 | 150 | 125 | 131 | 1.7 | 1.7 | 1.7 |
| 35 | 180 | 150 | 162 | 1.2 | 1.2 | 1.2 |
| 50 | 215 | 175 | 197 | 0.9 | 0.9 | 0.9 |
| 70 | 265 | 215 | 251 | 0.6 | 0.6 | 0.6 |
| 95 | 315 | 260 | 304 | 0.5 | 0.5 | 0.5 |
| 120 | 360 | 300 | 353 | 0.4 | 0.4 | 0.4 |
| 150 | 405 | 335 | 406 | 0.3 | 0.3 | 0.3 |
| 185 | 460 | 380 | 463 | 0.3 | 0.3 | 0.3 |
| 240 | 530 | 440 | 546 | 0.2 | 0.2 | 0.2 |
| 300 | 590 | 495 | 628 | 0.2 | 0.2 | 0.2 |
| 400 | 667 | 570 | 728 | 0.2 | 0.2 | 0.2 |
3) Three cores with aluminum conductor
| Nominal area of conductor | Three Cores Aluminum Conductors | |||||
|---|---|---|---|---|---|---|
| Current Ratings | Approximate voltage drop per ampereper metre | |||||
| Direct in ground | In singleway ducts | Installed in air | Ground | Duct | Air | |
| mm² | amps | amps | amps | mV | mV | mV |
| 16 | 89 | 72 | 74 | 4.2 | 4.2 | 4.2 |
| 25 | 115 | 94 | 98 | 2.7 | 2.7 | 2.7 |
| 35 | 135 | 110 | 120 | 1.9 | 1.9 | 1.9 |
| 50 | 165 | 135 | 145 | 1.4 | 1.4 | 1.4 |
| 70 | 200 | 165 | 185 | 1.0 | 1.0 | 1.0 |
| 95 | 240 | 200 | 224 | 0.7 | 0.7 | 0.7 |
| 120 | 275 | 230 | 264 | 0.6 | 0.6 | 0.6 |
| 150 | 310 | 255 | 305 | 0.5 | 0.5 | 0.5 |
| 185 | 350 | 295 | 350 | 0.4 | 0.4 | 0.4 |
| 240 | 410 | 340 | 418 | 0.3 | 0.3 | 0.3 |
| 300 | 460 | 385 | 488 | 0.3 | 0.3 | 0.3 |
| 400 | 520 | 443 | 562 | 0.2 | 0.2 | 0.2 |
4) Four cores with copper conductor
| Nominal area of conductor | Four Cores Stranded Copper Conductors | |||||
|---|---|---|---|---|---|---|
| Current Ratings | Approximate voltage drop per ampereper metre | |||||
| Direct in ground | In singleway ducts | Installed in air | Ground | Duct | Air | |
| mm² | amps | amps | amps | mV | mV | mV |
| 16 | 115 | 94 | 99 | 2.5 | 2.5 | 2.5 |
| 25 | 150 | 125 | 131 | 1.7 | 1.7 | 1.7 |
| 35 | 180 | 150 | 162 | 1.2 | 1.2 | 1.2 |
| 50 | 215 | 175 | 197 | 0.9 | 0.9 | 0.9 |
| 70 | 265 | 215 | 251 | 0.6 | 0.6 | 0.6 |
| 95 | 315 | 260 | 304 | 0.5 | 0.5 | 0.5 |
| 120 | 360 | 300 | 353 | 0.4 | 0.4 | 0.4 |
| 150 | 405 | 335 | 406 | 0.3 | 0.3 | 0.3 |
| 185 | 460 | 380 | 463 | 0.3 | 0.3 | 0.3 |
| 240 | 530 | 440 | 546 | 0.2 | 0.2 | 0.2 |
| 300 | 590 | 495 | 628 | 0.2 | 0.2 | 0.2 |
| 400 | 667 | 570 | 728 | 0.2 | 0.2 | 0.2 |
| 500 | 720 | 605 | 800 | 0.2 | 0.2 | 0.2 |
4) Four cores with aluminum conductor
| Nominal area of conductor | Four Cores Aluminum Conductors | |||||
|---|---|---|---|---|---|---|
| Current Ratings | Approximate voltage drop per ampereper metre | |||||
| Direct in ground | In singleway ducts | Installed in air | Ground | Duct | Air | |
| mm² | amps | amps | amps | mV | mV | mV |
| 16 | 89 | 72 | 74 | 4.2 | 4.2 | 4.2 |
| 25 | 115 | 94 | 98 | 2.7 | 2.7 | 2.7 |
| 35 | 135 | 110 | 120 | 1.9 | 1.9 | 1.9 |
| 50 | 165 | 135 | 145 | 1.4 | 1.4 | 1.4 |
| 70 | 200 | 165 | 185 | 1.0 | 1.0 | 1.0 |
| 95 | 240 | 200 | 224 | 0.7 | 0.7 | 0.7 |
| 120 | 275 | 230 | 264 | 0.6 | 0.6 | 0.6 |
| 150 | 310 | 255 | 305 | 0.5 | 0.5 | 0.5 |
| 185 | 350 | 295 | 350 | 0.4 | 0.4 | 0.4 |
| 240 | 410 | 340 | 418 | 0.3 | 0.3 | 0.3 |
| 300 | 460 | 385 | 488 | 0.3 | 0.3 | 0.3 |
| 400 | 520 | 443 | 562 | 0.2 | 0.2 | 0.2 |
| 500 | 561 | 470 | 618 | 0.2 | 0.2 | 0.2 |
Electrical Properties(1900/3300 V)
| Nominal area of conductor | Single Core Stranded CopperConductors | Nominal area of conductor | Three Core Stranded CopperConductors | ||||
|---|---|---|---|---|---|---|---|
| Current Ratings | Current Ratings | ||||||
| Direct in ground | In single wayducts | Installed in air | Direct in ground | In single wayducts | Installed in air | ||
| mm² | amps | amps | amps | mm² | amps | amps | amps |
| 50 | 222 | 219 | 228 | 16 | 114 | 96 | 106 |
| 70 | 271 | 264 | 285 | 25 | 147 | 124 | 142 |
| 95 | 324 | 310 | 350 | 35 | 175 | 147 | 168 |
| 120 | 366 | 342 | 407 | 50 | 207 | 174 | 202 |
| 150 | 409 | 376 | 463 | 70 | 254 | 214 | 255 |
| 185 | 460 | 414 | 528 | 95 | 304 | 257 | 312 |
| 240 | 528 | 464 | 623 | 120 | 345 | 293 | 361 |
| 300 | 589 | 506 | 710 | 150 | 387 | 328 | 410 |
| 400 | 651 | 535 | 808 | 185 | 436 | 371 | 471 |
| 500 | 720 | 579 | 915 | 240 | 502 | 428 | 554 |
| 630 | 789 | 624 | 1030 | 300 | 563 | 480 | 634 |
| 800 | 831 | 650 | 1119 | - | - | - | - |
| 1000 | 880 | 689 | 1214 | - | - | - | - |