Highway Cables 
 

Highway Cables

Network Control Armoured Highway Cables

Application :
These cables are suitable for communication & signal transmission used in roadways and highways. Rugged constructions suitable for a variety of installations.

Conductor: Plain annealed stranded copper

Insulation: XLPE (Cross linked polyethylene)

Core Identification: brown, blue & green/yellow

Tape: polyester binding tape

Bedding: MDPE (Medium density polyethylene)

Armour/Protection: Galvanised SWA (Single wire armour)

Sheath/Jacket: MDPE (Medium density polyethylene)

Colour: Black

Voltage: 600/1000V

Standards: IEC60502

Size sq
(mm)

Min. Thickness of Inner Sheath
(mm)

Nominal Diameter of Armour Wire
(mm)

Min. Thickness of Oversheath
(mm)

Max. Overall Diameter
(mm)
Copper Conductor Resistance
(Ohm)
Max. Current Rating Laid in Ground
(AMP)
Voltage Drop/m. @ Rated Current
(MV)
10
1.0
1.25
1.8
19.5
1.83
92
4.1

25

1.0

1.60

1.8

27.0
0.727
152
1.65