| RG62 LSF | ||||||||||||
| Product Name/Code : RG62 LSF | Electrical Performance | |||||||||||
| Application : | Electrical Characteristics: | |||||||||||
| For communication and signal control systems. | Frequency | Attenuation | ||||||||||
| Reference Standard | (MHz) | (dB/100m) | ||||||||||
| Customer's sample spec. and the general standard | 50 | 6.1 | ||||||||||
| 100 | 9.9 | |||||||||||
| Cable Construction | 200 | 12.7 | ||||||||||
| Center Conductor | CCS | 400 | 20.5 | |||||||||
| Dia. | 1/0.643 | 700 | 26.9 | |||||||||
| Insulation | Tube PE | 900 | 29.4 | |||||||||
| Nom. Thickness(mm) | 1.5 | 1000 | 31.5 | |||||||||
| Insulation Dia. (±0.03mm) | 4.6 | Operating Temperature( ? ) | 60 | |||||||||
| Bare Copper Braid Shield | Capacitance(pF/m) | 44.5 | ||||||||||
| Construction | 16/ 7/0.12 | Velocity ratio (+/-5%) | 66.7 | |||||||||
| Coverage Area(%) | >=86 | Impedance(+/-3 Ω ) | 93 | |||||||||
| Jacket | LSF | |||||||||||
| Nom. Thickness(mm) | 0.78 | |||||||||||
| Cable Dia.(±0.10mm) | 6.15 | 
 | 
 | |||||||||
| Jacket Compound | PVC/LSF/LSOH | 
 | 
 | |||||||||
| Core Identification/Color Code | According to customer request | 
 | 
 | |||||||||
| Bending Radius | 6 x Overall Diameter | 
 | 
 | |||||||||
| Temperature Rating | 70 ℃ | 
 | 
 | |||||||||
| Voltage Rating | 300/500V | 
 | 
 | |||||||||
| Fire Performance | 
 | 
 | 
 | |||||||||
| 
 | 
 | 
 | ||||||||||