P15 UX 0.6/1kV

Applications

These cables are flame retardant, low smoke and halogen free, used for earthing and bonding services.

Standards

  • IEC 60092-353
  • IEC 60092-359
  • IEC 60332-1
  • IEC 60332-3-22
  • IEC 60754-1,2
  • IEC 61034-1,2
  • NEK 606:2004

Construction

P15 UX 0.6/1kV P15 UX 0.6/1kV
Conductors Tinned annealed stranded copper to IEC 60228 class 2 or class 5.
Insulation Halogen free thermosetting compound, SHF2.
  When used as protective earth (PE) wire, the cables coloured yellow/green.
  When used as single wire, the cables coloured off-white, black, red or blue.

Electrical Characteristics

Nominal Cross Section Area mm² 10 16 25 35 50 70
Nominal Conductor Diameter mm 4 5.1 6.5 7.4 8.7 10.3
Maximum DC Resistant@20℃ Ω/km 1.84 1.16 0.734 0.529 0.391 0.27
Continuous Current Rating@45℃1 Core A 72 96 127 157 196 242
Short Circuit Current 1s A 1430 2290 3580 5010 7150 10020
Operating Voltage KV 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1
Nominal Cross Section Area mm² 95 120 150 185 240 300
Nominal Conductor Diameter mm 12.2 13.8 15.1 17.0 19.6 21.9
Maximum DC Resistant@20℃ Ω/km 0.195 0.154 0.126 0.1 0.0762 0.0607
Continuous Current Rating@45℃1 Core A 293 339 389 444 522 601
Short Circuit Current 1s A 13590 17170 21460 26470 34340 42930
Operating Voltage KV 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1

Mechanical and Thermal Properties

Bending Radius 8×OD (during installation)
  6×OD (fixed installed)
Temperature Range -20℃ ~ +90℃

Dimensions and Weight

Construction No. of cores×Cross section(mm²) Nominal Insulation Thickness (mm) Nominal Overall Diameter (mm) Nominal Weight (kg/km)
1×10 1.0 6.6 125
1×16 1.0 7.7 185
1×25 1.2 9.5 290
1×35 1.2 10.4 380
1×50 1.4 12.1 510
1×70 1.4 13.6 700
1×95 1.6 15.5 950
1×120 1.6 17.5 1205
1×150 1.8 19.4 1470
1×185 2.0 21.7 1875
1×240 2.2 24.7 2420
1×300 2.4 27.2 3060