Application and Description :

TR2161 Non-armoured Energy Cable is a motorway cable sheathed with medium density polyethyylene (MDPE) designed for street lighting.

Standard :

IEC 60502, BS 5467

Cable Construction:

- Conductor: Plain annealed stranded copper conductor, comply with IEC 60228 for Class 2
- Insulation: Cross linked polyethylene (XLPE)
- Core Identification: Brown, Blue, Green/Yellow
- Inner Sheath: Medium density polyethylene (MDPE), comply with IEC 60708.
- Armor (for Armoured Cable Only): Galvanized steel wires
- Outer Sheath: Medium density polyethylene (MDPE), comply with IEC 60708.
- Sheath Color: Black

Technical Characteristics :

- Rated voltage: 600/Kft volts
- Minimum bending radius: 12 x ?
- Rated temperature: +90o C
- Conductor resistance:

CONDUCTOR SIZE MM2 10 25 50 70 95 120 150
RESISTANCE OHMS/ KM 1.83 0.727 0.387 0.268 0.193 0.153 0.124

- Current rating in duct:

CONDUCTOR SIZE MM2 10 25 50 70 95 120 150
CURRENT RATING A 92 152 217 266 319 330 406

- Volt drop :

CONDUCTOR SIZE MM2 10 25 50 70 95 120 150
VOLT DROP MV/M 4.1 1.65 0.87 0.6 0.45 0.37 0.3

Cable Parameter :

NUMBER OF PAIRS NOMINAL CONDUCTOR AREA NOMINAL CONDUCTOR STRANDING INNER SHEATH THICKNESS ARMOUR THICKNESS OUTER SHEATH THICKNESS NOMINAL O/D APPROX CABLE WEIGHT
MM2 NO./MM MM MM MM MM KG/KM
3 10 7/1.35 1.0 1.25 1.8 19.1 881
3 25 7/2.14 1.0 1.60 1.8 24.9 1703
3 50 19/1.78 1.0 1.60 2.0 30.7 2660
3 70 19/2.14 1.0 1.60 2.0 34.6 3489
3 95 19/2.52 1.2 2.0 2.2 40.7 4903
3 120 37/2.03 1.2 2.0 2.3 44.4 5891
3 150 37/2.25 1.4 2.5 2.5 50.0 7521