CCL-9309
Product Name/Code: 9309 Electrical Performance
Application: Max. inner Conductor Resistance £¨¦¸/Km£© 54.8
Multi-Conductor-Audio, Control, & Instrumentation Cables Voltage Rating(V) 300
Construction
9PAIRS(18CORES) Stranded Tinned Copper
AWG 22 Capacitance (pF/m) C1 110
Construction Solid Capacitance (pF/m) C2 160
Conductor Diameter (mm) 0.64    
Insulation PVC/PE/PP/XLPE/LSF/LSOH    
Thickness 0.60    
Insulation Diameter(mm) 1.84    
Insulation Color

Black &Red

   
Drain wire Stranded Tinned Copper    
AWG 22    
Construction 7x0.20    
Over all Screen AL/PET    
Construction Multipair overall laid up in aluminum-Foil Polyester Tape Screen    
Sheath PVC/LSF/LSOH    
Thickness(mm) 0.8    
Diameter(mm) 9.6    
Core Identification/Color Code According to customer request    
Bending Radius 6xOverall Diameter    
Operating Temperature( ¡æ ) -20/80    
Fire Performance
   
Flame Propagation Test to IEC 60332 Part 1 and Part 3
Determination of the amount Halogen Acid Gas to IEC 60754 Part 1
Smoke Density Test to IEC 61034
Oxygen Index Test to BS 2863 or ISO 4589-2
Temperature Index Test to BS 2782 or ISO 4589-3
Fire Resistant Test to IEC 60331-24
   

website: www.caledonian-cables.com