Home
Chi siamo
Prodotti
Scaricare
Biblioteca tecnica
Contatto
Richiesta
Mappa del sito 
Collegamenti
 

Allarme & Cavo Audio & Elettronico

Cavo di Equivalente di Belden

Cavo coassiale

Cavo di Controllo

Cavo Fibra Ottica

Cavo Flessibile

Cavo strumentazione

Cavi LAN
Cavo Energia
Cavo Ferroviario

Robotic

Cavo per Materiale Rotabile
Cavo di gomma
Cavo di Sicurezza

Cavo Telefonico

Aeroporto Cavi

Bus Cavi

Serracavi

Data Cable

Calore di rilevamento Cavi
Cavi ad alta temperatura
Cavi autostrada
Marine, OIL,GAS & Petrochemical Cables
Cavi Speciali
Cavi a spirale
Termocoppia Cavi
     
  indoor tight buffer fiber optic cable  
Indoor Used Tight Buffered Fiber
Optical Cable
outdoor multi loose tube fiber optic cable
Outdoor Used Multi Loose Tube
Fiber Optical Cable
 
  Cavo Energia  

Cavo Energia

BS 6622 Single Core Unarmoured (Copper Wire Screened) 6.6kV XLPE Stranded Copper Conductors

Edilizia

cross-sectional area mmsq

Minimum average thickness of insulation mm

Nominal diameter over insulation
mm

 

Nominal area of copperwire screen mmsq

Nominal average thickness of PVC oversheath
mm

Nominal overall diameter of cable mm

50

2.5

15.0

16.0

1.6

21.7

70

2.5

16.8

16.0

1.7

23.5

95

2.5

18.5

16.0

1.7

25.4

120

2.5

20.0

16.0

1.8

26.9

150

2.5

21.3

16.0

1.8

28.5

185

2.5

23.1

16.0

1.9

30.3

240

2.6

25.5

25.0

1.9

32.9

300

2.8

28.3

25.0

2.0

35.9

400

3.0

31.4

35.0

2.2

39.2

500

3.2

34.7

35.0

2.3

42.8

630

3.2

38.1

35.0

2.4

46.5

800

Please refer to our technical department for further information

1000

Installation

cross-sectional area mmsq

Approximate cable weight kg/m

Nominal drum length
m

Minimum bending radius mm

Nominal internal diameter of ducts mm

50

0.9

1000

350

100

70

1.1

1000

400

100

95

1.4

1000

400

100

120

1.7

1000

450

100

150

2.0

500

450

100

185

2.4

500

500

100

240

3.0

500

500

100

300

3.6

500

550

100

400

4.5

500

600

100

500

5.6

500

650

100

630

6.9

300

700

100

800

Please refer to our technical departmen for further information

1000

Performance Elettrica

cross-sectional area mmsq

Maximum DC resistance of conductor at 20 ℃ uohms/m

Maximum AC resistance of conductor at 90 ℃ uohms/m

Reactance at 50Hz
uohms/m

Impedance at 50Hz uohms/m

Maximum Capacitace PF/m

Maximum charging current at normal voltage and frequency mA/m

50

387

494

123.0

508.0

321.0

0.39

70

268

343

115.0

361.0

371.0

0.45

95

193

248

109.0

270.0

417.0

0.50

120

153

196

105.0

222.0

459.0

0.55

150

124

159

103.0

189.0

494.0

0.59

185

99.1

128

99.5

162.0

543.0

0.65

240

75.4

98

96.6

138.0

583.0

0.70

300

60.1

80

94.7

124.0

602.0

0.72

400

47.0

64

92.5

112.0

627.0

0.75

500

36.6

51

90.7

104.0

654.0

0.79

630

38.3

42

88.0

97.1

726.0

0.87

800

Please refer to our technical department for further information

1000

Ratings

Cross-sectional area
mmsq

Current Ratings

Short circuit ratings

Laid direct in ground
Amps

Drawn into ducts
Amps

Laid in air
Amps

One second short circuit rating of conductor
KA

One second short circuit rating of copper per core
KA

50

220

225

250

6.8

2.6

70

270

270

310

9.8

2.6

95

320

320

375

13.3

2.6

120

360

360

430

17.2

2.6

150

410

400

490

21.2

2.6

185

460

440

560

26.6

2.6

240

530

505

660

34.9

4.3

300

600

560

760

43.8

4.3

400

680

610

880

57.3

5.8

500

750

680

1000

72.3

5.8

630

830

750

1140

91.2

5.8

800

Please refer to our technical department for further information

1000